Thermo King Trailer Repair
Thermo King reefer trailers are the most common types of mobile refrigerators in the US. Here, at Find Trucks Services Center, you can get a premium Thermo King trailer repair, performed by professional mechanics. We have gathered an experienced team of ASE certified technicians with years of experience. Modern, state-of-art equipment assures high-quality and meticulous reefer repair and maintenance.
If you are in The United States and Canada and require a qualified Thermo King repair, feel free to contact us. For the most comprehensive truck and trailer repair provider in The United States and Canada. You can trust your reefer trailer to us.
Our refrigeration mechanics have experience servicing the following units, among many others:
For Trailers:
- Spectrum DE with SR-2
- Spectrum SB with SR-2
- SB-400
- SB-230 & SB-330
- Super-II
- SB-200TG
- SB-190
- SB-210+ & SB-310+
- SB III-SP & SB III-SR+
For Trucks:
- MD-100
- T-600 & T-600R
- T-800 & T-800R
- TS-200, TS-300 & TS-500
- RD-II SP & MD-II SR
- T-1000 & T-1000R
- UT-1200X
- T-1000 Spectrum
Ask us for information regarding some of the latest Thermo King products to hit the market:
- Sensor Kits – for monitoring and controlling temperature
- Secondary Door Latch Kit – for extra security
- System Clean Up Kit – revolutionary way to clean refrigeration system clean up
- Coupler Brushing Kit – extends life of coupler brushings
- Smooth Air Blower – can lower fuel usage by up to 7%
Let us keep your Thermo King units in the best possible shape!
Thermo King Repair Shop
Repair shops that provide reefer trailer repair are pretty rare. If you are looking for a reliable Thermo King repair 24 Hours facilities in The United States and Canada , Find Trucks Services Vendors Center is your go-to place. We have created a convenient station to satisfy the trucker’s needs.
Don’t waste your time looking for a service to hold on, just call us and get everything you require.
Thermo King Repair Service
Thermo King repair, as any reefer equipment repair, requires a lot of effort and professionalism. Proper mend and maintenance for Thermo King equipment mean correct temperature regulation that required for reefer trailers. This is the main necessity to get yourself good loads to haul.
Carrier Refrigeration Unit Repair
Carrier Transicold - a key link in the chain of life. Our refrigerated transport solutions help to improve daily life for everyone. Carrier Transicold helps improve transport of temperature controlled goods with a complete line of equipment and services for refrigerated transport and cold chain visibility. For more than 45 years, Carrier Transicold has been an industry leader, providing customers around the world with advanced, energy-efficient and environmentally sustainable trailer refrigeration systems for light commercial vehicles, trucks and trailers.
Carrier is one of the widely distributed refrigerator equipment manufacturers. It is not a secret that without properly functioning equipment, the trucker won’t get loads. Quality reefer (Carrier, in particular) equipment repair is sometimes hard to find because not every facility provides such a service.
Here, at Find Trucks Services Truck Center, we give you the widest spectrum of truck repair and maintenance services. Carrier refrigeration unit repair is one of them. Our experienced team of mechanics can handle any task.
highly trained service mechanics has been servicing the following models, among others, for the greater Chicago area:
Additionally, as new technology becomes available for the mobile refrigeration industry, you may be interested in staying up to date on the latest innovations. Often these have great long-term benefits for cost, efficiency, competition and ease of use. TKX values staying plugged in with the way technology is moving the industry forward.
Recent developments from Carrier Transicold:
- Vector Hybrid technology and all-electric units offer better fuel efficiency and environmental friendliness.
- The Carrier Transicold APX Control System integrates the latest technology with tried and true refrigerated methods to create an easy to use, reliable and efficient method of regulating temperatures for trucks and trailers. Some notable features:
- The industry’s first decentralized control system
- CAN-bus communication
- Smaller, more compact electrical system with fewer components
- Sophisticated temperature regulation software
- Reefer Apps with extended special features
- Intuitive dashboard-style display
- ATM-style interface with message center and choice of language
Carrier Trailer Repair Shop
Not every repair shop offers full overhaul for reefer trailers. anywhere in The United States and Canada will be your reefer repair solutions . We have gathered a great team of ASE certified technicians who are qualified to perform Carrier equipment repairs. State-of-art equipment allows performing any service in a matter of time.
Our facility is a well-established hub that can fit the whole fleet. We created a place where truckers and fleet owners can have top-notch service for any type of truck and trailer.
Carrier Trailer Repair Service
Don’t waste your time looking for someone who can handle Carrier trailer maintenance. Find Trucks Services Center is already here to provide you the finest service everywhere in The United States and Canada. Feel free to contact us and schedule your visit.
Carrier Delivers Freshness and Reliability
Carrier understands that “fresh” is not simply about how recently produce was harvested or products were created. It is also about the conditions in which they have been transported. That is why we provide transport refrigeration solutions that allow for precise control of temperature and humidity, preserving all types of perishable cargo no matter where it needs to go.
Transport Refrigeration By Land
Featuring next-generation technologies, Carrier Transicold sets ever-higher standards in refrigerated container, truck and trailer systems while reducing fuel consumption, emissions and sound levels.
Transport Refrigeration By Sea
For more than 40 years, Carrier Transicold has been the industry leader in marine container refrigeration. We are the preferred supplier of innovative, reliable container refrigeration systems for the world’s shipping lines and leasing customers.
Parts and Service Support Keeps You Moving
The sun never sets on Carrier Transicold’s parts coverage. With more than 600 dealers, distributors and parts depots worldwide, Carrier Transicold provides all the parts and related service support needed to keep our customers moving across roads, rails and waterways around the world.
TRS Transportkoeling B.V Is Now Part Of Carrier Transicold
Founded in 1981, TRS Transportkoeling b.v. (TRS) has grown from a local service organization to an international producer of sustainable transport refrigeration systems for trucks, containers and controlled atmosphere refrigerated transport. Carrier Transicold, an industry leader in the transport refrigeration business, has announced the acquisition of the Dutch manufacturer and service provider.
Repair Capabilities
No matter the make or model, our teams of technicians in The United States and Canada are ready to perform high-quality repairs. Some locations feature a full roof mezzanine. Our capabilities include:
- Bottom Rail Replacement
- Roll-up and swing door repair and replacement
- Reefer rebuilds and repair
- New reefer unit installation
- Preventative maintenance
- APU service
- In-house fabrication including aluminum and stainless
Reefer Service
Our Refrigeration Service Department technicians are knowledgeable, reliable and solve your refrigerated needs the first time. We understand that keeping your reefer running cool and at its peak condition is critical. Our experienced mechanical staff will quickly diagnose and repair your unit, so you experience less down time. Nothing is too big or small for our shop, whether you simply need an oil change or an entire refrigeration unit replaced, we can handle the job. In addition, we provide mobile services, and over the counter refrigeration parts sales for your convenience.
Carrier Transicold Alarm Codes
Carrier Transicold Straight Truck Units – Most Popular
# 1 Supra 550
# 2 Supra 650
#3 Supra 750
# 4 Supra 850
# 5 Supra 950
Carrier Transicold Trailer Truck Units – Most Popular
# 1 Ultima 53
# 2 Ultima XT /XTC
# 3 XT/XTC
# 4 X 2100
# 5 X 2200
# 6 X 2500
Carrier Transicold Alarm Codes Defined:
- 1 LOW LEVEL FUEL
- 2 LOW ENGINE OIL LEVEL
- 3 LOW COOLANT LEVEL
- 11 LOW ENGINE OIL PRESSURE
- 12 HIGH COOLANT TEMPERATURE
- 13 HIGH DISCHARGE PRESSURE
- 15 BATTERY VOLTAGE TOO HIGH
- 16 BATTERY VOLTAGE TOO LOW
- 17 HIGH COMP DISCHARGE TEMP
- 18 LOW REFRIGERANT PRESSURE
- 28 CHECK REFRIGERATION SYSTEM
- 30 FAILED TO RUN MINIMUM TIME
- 31 FAILED TO START- AUTO MODE
- 32 FAILED TO START- MANUAL
- 34 ENGINE FAILED TO STOP
- 35 CHECK STARTER CIRCUIT
- 36 CHECK COOLANT TEMPERATURE
- 37 CHECK LOW SPEED RPMs
- 38 CHECK HIGH SPEED RPMs
- 39 CHECK ENGINE RPM
- 40 CHECK GLOW PLUGS
- 41 ENGINE STALLED
- 51 ALTERNATOR NOT CHARGING
- 53 BOX TEMP OUT- OF- RANGE
- 54 DEFROST NOT COMPLETE
- 55 CHECK DRFROST AIR SWITCH
- 56 CHECK AIRFLOW
- 57 CHECK REMOTE SWITCH 1
- 58 CHECK REMOTE SWITCH 2
- 59 DATALOGGER NOT RECORDING
- 60 DATALOGGER TIME WRONG
- 61 DOOR OPEN
- 71 BAD F2 OR F3 FUSE
- 78 CHECK SV1 CIRCUIT
- 80 CHECK SV3 CIRCUIT
- 81 CHECK FHR CIRCUIT
- 82 CHK REMOTE OUT-RANGE LIGHT
- 83 CHECK REMOTE DEFROST LIGHT
- 84 CHECK REMOTE ALARM LIGHT
- 85 CHECK UL1 UNLOADER
- 86 CHECK UL2 UNLOADER
- 87 CHECK REMOTE HEAT LIGHT
- 88 CHECK REMOTE COOL LIGHT
- 89 CHECK REMOTE AUTO LIGHT
- 93 CHECK START UP BUZZER
- 97 CHECK SV2 CIRCUIT
- 121 CHECK AMBIENT AIR SENSOR
- 122 CHECK RETURN AIR SENSOR
- 123 CHECK SUPPLY AIR SENSOR
- 124 CHECK DEFROST TERM 1 SENSOR
- 125 CHECK COMP DISCHARGE SENSOR
- 126 CHECK FUEL ENSOR CIRCUIT
- 129 CHECK ENGINE COOLANT SENSOR
- 130 CHECK ENGINE RPM SENSOR
- 132 CHECK DEFROST TERM 2 SENSOR
- 133 CHECK REMOTE TEMP SENSOR
- 134 CHECK REMOTE TEMP SENSOR
- 135 CHECK REMOTE TEMP SENSOR 3
- P141 PRETRIP STOPPED BY USER
- P143 CHECK CLUTCH CIRCUIT
- P144 CHECK UL1 CIRCUIT
- P145 CHECK SPEED SOLENOID CIRCUIT
- P148 CHECK SV1 CIRCUIT
- P149 CHECK SV3 CIRCUIT
- P150 CHECK SV4 CIRCUIT
- P151 CHECK GLOW PLUG CIRCUIT
- P152 CHECK FUEL SOLENOID CIRCUIT
- P153 CHECK RETURN AIR SENSOR
- P154 CHECK SUPPLY AIR SENSOR
- P155 CHECK COLLANT TEMP SENSOR
- P156 CHECK BATTERY VOLTS
- P157 CHECK BATTERY CURRENT
- P158 CHECK AMBIENT AIR SENSOR
- P159 CHECK DEFROST TERM 1 SENSOR
- P160 CHECK DISCHARGE TEMP SENSOR
- P164 CHECK UL2 CIRCUIT
- P165 CANNOT PUMP DOWN
- P 174 CHECK LOW SPEED RPM
- P175 CHECK HIGH SPEED RPMs
- P178 CHECK UL1 UNLOADER
- P181 CHECK SV4 VALVE
- P182 CHECK SV1 VALVE
- P183 CHECK SV3 VALVE
- P191 CHECK UL2 UNLOADER
- P192 CHECK SV2 CIRCUIT
- P194 HIGH SUCTION PRESSURE
- P195 LOW SUCTION PRESSURE
- P196 HIGH DISCHARGE PRESSURE
- P198 LOW DISCHARGE PRESSURE
- P200 CHECK FRONT CYLINDERS
- P201 CHECK REAR CYLINDERS
- P202 HIGH SIDE LEAK
- P203 CHECK DISCHARGE CHECK VALVE
- P204 LOW SUCTION PRESSURE
- P205 CHECK DEFROST TERM 2 SENSOR
- 223 ENGINE MAINTENANCE DUE
- 225 GENERAL MAINTENANCE DUE
- 226 SERVICE SOON-PM # 1 DUE
- 227 SERVICE SOON-PM # 2
- 228 SERVICE SOON-PM # 3
- 229 SERVICE SOON-PM # 4
- 230 SERVICE SOON-PM # 5
- 232 SETPOINT ERROR
- 233 MODEL # ERROR
- 234 UNIT SERIAL # ERROR
- 235 CONTORL SERIAL # ERROR
- 236 TRAILER # ERROR
- 237 FUNCTIONAL PARAMETERS ERROR
- 238 CONFIGURATIONS 1 ERROR
- 239 CONFIGURATIONS 2 ERROR
- 240 HOUR METER ERROR
- 241 ALARM STSTUS ERROR
- 242 DIS PRESS CALIBRATE ERROR
- 243 SUCT/EVAP CALIBRATE ERROR
- 245 MICRO SW REV ERROR
- 246 EEPROM WRITE FAILURE
- 247 CONFIGURATIONS 3 ERROR
- 248 CONFIG MODE/ HP2 ERROR
- 249 MICROPROCESSOR ERROR
Thermo King Alarm Codes - North America
This is a listing of all current truck, trailer, CR, DAS and DSR alarm codes. On multi-temp units, the zone will be identified. Please record all alarms that occur to assist technician in resolving issue. Alarm codes with parenthesis (XX) may exist with alarm code 84 and may clear automatically.
THERMO KING TRUCK, TRAILER, CR, DAS, AND DSR ALARM CODES
00
Status: Green = OK to Run
Description: No Alarms Exist
Operator Action: No action required.
02
Status: Yellow = Check as Specified
Description: Check Evaporator Coil Sensor (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
03
Status: Yellow = Check as Specified
Description: Check (Control) Return Air Sensor (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
04
Status: Yellow = Check as Specified
Description: Check (Control) Discharge Air Sensor (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
05
Status: Green = OK to Run
Description: Check Ambient Temp Sensor
Operator Action: Report alarm at end of day.
06
Status: Green = OK to Run
Description: Check Coolant Temp Sensor
Operator Action: Report alarm at end of day.
07
Status: Green = OK to Run
Description: Check Engine RPM Sensor
Operator Action: Report alarm at end of day.
08
Status: Yellow = Check as Specified
Description: Unit Running on Coil Sensor (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
(09)
Status: Yellow = Check as Specified
Description: High Evaporator Temperature (Zone)
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
(10)
Status: Red = Take Immediate Action
Description: High Discharge Pressure (or Temperature)
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
11
Status: Yellow = Check as Specified
Description: Unit or Zone Controlling on Alternate Sensor (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
12
Status: Red = Take Immediate Action
Description: Sensor or Digital Input Shutdown (Zone)
Operator Action: Unit/zone cannot operate and is shut down. Repair immediately.
13
Status: Yellow = Check as Specified
Description: Sensor Check (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
14
Status: Green = OK to Run
Description: Defrost Terminated by Time
Operator Action: Report alarm at end of day.
15
Status: Yellow = Check as Specified
Description: Check Glow Plugs or Intake Air Heater
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
16
Status: Green = OK to Run
Description: Manual Start Not Completed
Operator Action: Report alarm at end of day.
(17)
Status: Yellow = Check as Specified
Description: Engine Failed to Crank
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
(18)
Status: Yellow = Check as Specified
Description: High Engine Coolant Temperature
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
(19)
Status: Yellow = Check as Specified
Description: Low Engine Oil Pressure
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
(20)
Status: Yellow = Check as Specified
Description: Engine (Vapor Motor CR) Failed to Start
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
(21)
Status: Yellow = Check as Specified
Description: Cooling Cycle Check (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
(22)
Status: Yellow = Check as Specified
Description: Heating Cycle Check (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
23
Status: Red = Take Immediate Action
Description: Cooling Cycle Fault (Zone)
Operator Action: Unit/zone cannot operate and is shut down. Repair immediately.
24
Status: Red = Take Immediate Action
Description: Heating Cycle Fault (Zone)
Operator Action: Unit/zone cannot operate and is shut down. Repair immediately.
25
Status: Yellow = Check as Specified
Description: Alternator Check
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
(26)
Status: Yellow = Check as Specified
Description: Check Refrigeration Capacity (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
(27)
Status: Red = Take Immediate Action
Description: Vapor Motor RPM High (CR)
Operator Action: Unit cannot operate and is shut down. Repair immediately.
28
Status: Green = OK to Run
Description: Pretrip or Self Check Abort
Operator Action: Report alarm at end of day.
29
Status: Yellow = Check as Specified
Description: Defrost Damper Circuit Check (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
30
Status: Red = Take Immediate Action
Description: Defrost Damper Stuck Closed (Zone)
Operator Action: Unit/zone cannot operate and is shut down. Repair immediately.
31
Status: Yellow = Check as Specified
Description: Check Oil Pressure Switch
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
32
Status: Red = Take Immediate Action
Description: Refrigeration Capacity Low (Zone)
Operator Action: Unit/zone cannot operate and is shut down. Repair immediately.
33
Status: Green = OK to Run
Description: Check Engine RPM
Operator Action: Report alarm at end of day.
34
Status: Yellow = Check as Specified
Description: Check Modulation Circuit
Operator Action: Manually monitor temperature. Report alarm at end of day.
35
Status: Red = Take Immediate Action
Description: Check Run Relay Circuit
Operator Action: Unit cannot operate and is shut down. Repair immediately.
(36)
Status: Red = Take Immediate Action
Description: Electric Motor Failed to Run
Operator Action: Unit cannot operate and is shut down. Repair immediately. Switch to Diesel Mode
37
Status: Green = OK to Run
Description: Check Engine Coolant Level
Operator Action: Report alarm at end of day.
38
Status: Red = Take Immediate Action
Description: Electric Phase Reversed
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
39
Status: Yellow = Check as Specified
Description: Check Water Valve Circuit
Operator Action: Manually monitor temperature. Report alarm at end of day.
40
Status: Yellow = Check as Specified
Description: Check High Speed Circuit
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
41
Status: Yellow = Check as Specified
Description: Check Engine Coolant Temp
Operator Action: Report alarm at end of day.
42
Status: Yellow = Check as Specified
Description: Unit Forced to Low Speed
Operator Action: Report alarm at end of day.
43
Status: Green = OK to Run
Description: Unit Forced to Low Speed Modulation
Operator Action: Report alarm at end of day.
44
Status: Red = Take Immediate Action
Description: Check Fuel System
Operator Action: Add fuel as necessary. Otherwise, report alarm at end of day.
45
Status: Yellow = Check as Specified
Description: Check Hot Gas or Hot Gas Bypass Circuit
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
46
Status: Yellow = Check as Specified
Description: Check Air Flow (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
47
Status: Red = Take Immediate Action
Description: Remote Sensor Shutdown
Operator Action: Unit/zone cannot operate and is shut down. Repair immediately.
48
Status: Red = Take Immediate Action
Description: Check Belts or Clutch
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
49
Status: Green = OK to Run
Description: Check Spare Sensor 1
Operator Action: Report alarm at end of day.
50
Status: Green = OK to Run
Description: Reset Clock
Operator Action: Report alarm at end of day.
51
Status: Red = Take Immediate Action
Description: Check Shutdown Circuit
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
52
Status: Yellow = Check as Specified
Description: Check Heat Circuit (Zone)
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
53
Status: Yellow = Check as Specified
Description: Check Economizer Valve Circuit
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
54
Status: Green = OK to Run
Description: Test Mode Timeout
Operator Action: Clear alarm and restart unit.
55
Status: Green = OK to Run
Description: Check Engine Speeds
Operator Action: Report alarm at end of day.
56
Status: Yellow = Check as Specified
Description: Check Evaporator Fan Low Speed (Zone)
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
57
Status: Yellow = Check as Specified
Description: Check Evaporator Fan High Speed (Zone)
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
61
Status: Yellow = Check as Specified
Description: Low Battery Voltage
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
62
Status: Red = Take Immediate Action
Description: Ammeter Out of Calibration
Operator Action: Unit cannot operate and is shut down. Repair immediately.
(63)
Status: Red = Take Immediate Action
Description: Engine or Vapor Motor Stopped
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
64
Status: Green = OK to Run
Description: Pretrip Reminder
Operator Action: Report alarm at end of day.
65
Status: Yellow = Check as Specified
Description: Abnormal Temperature Differential (Zone)
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
66
Status: Red = Take Immediate Action
Description: Low Engine Oil Level
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
67
Status: Yellow = Check as Specified
Description: Check Liquid Line Solenoid Circuit (Zone)
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
68
Status: Red = Take Immediate Action
Description: Internal Controller Fault Code
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
70
Status: Green = OK to Run
Description: Hourmeter Failure
Operator Action: Report alarm at end of day.
71
Status: Green = OK to Run
Description: Hourmeter 4 Exceeds Set Time Limit
Operator Action: Report alarm at end of day.
72
Status: Green = OK to Run
Description: Hourmeter 5 Exceeds Set Time Limit
Operator Action: Report alarm at end of day.
73
Status: Green = OK to Run
Description: Hourmeter 6 Exceeds Set Time Limit
Operator Action: Report alarm at end of day.
74
Status: Green = OK to Run
Description: Controller Reset to Defaults
Operator Action: Report alarm at end of day.
75
Status: Red = Take Immediate Action
Description: Controller RAM Failure
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
76
Status: Red = Take Immediate Action
Description: Controller EPROM Failure
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
77
Status: Red = Take Immediate Action
Description: Controller EPROM Checksum Failure
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
78
Status: Red = Take Immediate Action
Description: Data Log EPROM Failure
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
79
Status: Green = OK to Run
Description: Internal Data Logger Overflow
Operator Action: Report alarm at end of day.
80
Status: Green = OK to Run
Description: Check Compressor Temp Sensor
Operator Action: Report alarm at end of day.
81
Status: Red = Take Immediate Action
Description: High Compressor Temp
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
82
Status: Red = Take Immediate Action
Description: High Compressor Temp Shutdown
Operator Action: Unit cannot operate and is shut down. Repair immediately.
83
Status: Green = OK to Run
Description: Low Engine Coolant Temp
Operator Action: Report alarm at end of day.
84
Status: Green = OK to Run
Description: Restart Null
Operator Action: Report alarm at end of day.
85
Status: Green = OK to Run
Description: Forced Unit Operation
Operator Action: Report alarm at end of day.
86
Status: Green = OK to Run
Description: Check Discharge Pressure Sensor
Operator Action: Report alarm at end of day.
87
Status: Green = OK to Run
Description: Check Suction Pressure Sensor
Operator Action: Report alarm at end of day.
88
Status: Green = OK to Run
Description: Reserved for CR
89
Status: Green = OK to Run
Description: Check Electronic Throttling Valve (ETV) Circuit
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
90
Status: Green = OK to Run
Description: Electric Overload
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
91
Status: Green = OK to Run
Description: Check Electric Ready Input
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
92
Status: Green = OK to Run
Description: Sensor Grades Not Set (Zone)
Operator Action: Report alarm at end of day.
93
Status: Green = OK to Run
Description: Low Compressor Suction Pressure
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
94
Status: Green = OK to Run
Description: Check Loader #1 Circuit
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
95
Status: Green = OK to Run
Description: Check Loader #2 Circuit
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
96
Status: Yellow = Check as Specified
Description: Low Fuel Level
Operator Action: Add fuel as required.
97
Status: Red = Take Immediate Action
Description: Failed Remote Return Air Sensor (CR)
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
98
Status: Green = OK to Run
Description: Check Fuel Level Sensor
Operator Action: Report alarm at end of day.
99
Status: Red = Take Immediate Action
Description: High Compressor Pressure Ratio
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
(100)
Status: Yellow = Check as Specified
Description: Heater Fan Failure (CR)
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
101
Status: Red = Take Immediate Action
Description: Controlling on Evap Coil Outlet Temp (CR)
Operator Action: Manually monitor temperature. Report alarm at end of day.
(102)
Status: Yellow = Check as Specified
Description: Low Evaporator Coil Temperature (CR)
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
103
Status: Yellow = Check as Specified
Description: Low Heater Fuel Level (CR)
Operator Action: Manually monitor temperature. Report alarm at end of day.
104
Status: Yellow = Check as Specified
Description: Check Remote Fan Speed (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
105
Status: Yellow = Check as Specified
Description: Check Receiver Tank Press Sol Circuit
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
106
Status: Yellow = Check as Specified
Description: Check Purge Valve Circuit
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
107
Status: Yellow = Check as Specified
Description: Check Condenser Inlet Sol Circuit
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
108
Status: Yellow = Check as Specified
Description: Door Open Timeout (Zone)
Operator Action: Close doors. Report alarm at end of day.
109
Description: Check High Discharge Pressure Sensor
Operator Action: Replaced by Alarm Code 86
110
Status: Yellow = Check as Specified
Description: Check Suction Line Sol Circuit (Zone)
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
111
Status: Green = OK to Run
Description: Unit Not Configured Correctly (Zone)
Operator Action: Report alarm at end of day.
112
Status: Yellow = Check as Specified
Description: Check Remote Fans (Zone)
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
113
Status: Yellow = Check as Specified
Description: Check Electric Heat Circuit (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
114
Status: Red = Take Immediate Action
Description: Multiple Alarms - Can Not Run (Zone)
Operator Action: Unit/zone cannot operate and is shut down. Repair immediately.
115
Status: Yellow = Check as Specified
Description: Check High Pressure Cut Out Switch
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
116
Status: Green = OK to Run
Description: Check High Pressure Cut In Switch
Operator Action: Report alarm at end of day.
117
Status: Green = OK to Run
Description: Auto Switch from Diesel to Electric
Operator Action: Normal operation – does not affect performance.
118
Status: Green = OK to Run
Description: Auto Switch from Electric to Diesel
Operator Action: Normal operation – does not affect performance.
119
Description: Reserved for CR
120
Status: Yellow = Check as Specified
Description: Check Alternator Excite Circuit
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
121
Status: Yellow = Check as Specified
Description: Check PMW Liquid Injection Circuit
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
122
Status: Yellow = Check as Specified
Description: Check Diesel/Electric Circuit
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
123
Status: Yellow = Check as Specified
Description: Check Evap Coil Inlet Temp Sensor (CR)
Operator Action: Manually monitor temperature. Report alarm at end of day.
124
Status: Green = OK to Run
Description: Check Evap Coil Outlet Temp Sensor (CR)
Operator Action: Report alarm at end of day.
125
Status: Yellow = Check as Specified
Description: Check Tank Level Sensor (CR)
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
126
Status: Yellow = Check as Specified
Description: Check Back Pressure Regulator (CR)
Operator Action: Manually monitor temperature. Report alarm at end of day.
127
Status: Yellow = Check as Specified
Description: Setpoint Not Entered (Zone)
Operator Action: Be sure setpoint is adjusted to required temperature.
128
Status: Green = OK to Run
Description: Engine Run Time Maint Reminder #1/Service Due
Operator Action: Report alarm at end of day.
129
Status: Green = OK to Run
Description: Engine Run Time Maint Reminder #2
Operator Action: Report alarm at end of day.
130
Status: Green = OK to Run
Description: Engine Run Time Maint Reminder #1
Operator Action: Report alarm at end of day.
131
Status: Green = OK to Run
Description: Electric Run Time Maint Reminder #2
Operator Action: Report alarm at end of day.
132
Status: Green = OK to Run
Description: Total Unit Run Time Maint Reminder #1
Operator Action: Report alarm at end of day.
133
Status: Green = OK to Run
Description: Total Unit Run Time Maint Reminder #2
Operator Action: Report alarm at end of day.
134
Status: Green = OK to Run
Description: Controller Power On Hours
Operator Action: Report alarm at end of day.
135
Status: Green = OK to Run
Description: Check Spare Digital Inputs
Operator Action: Report alarm at end of day.
136
Status: Green = OK to Run
Description: Check Spare Digital Outputs
Operator Action: Report alarm at end of day.
137
Status: Yellow = Check as Specified
Description: Check Damper Motor Heater Output
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
138
Status: Green = OK to Run
Description: Log DAS Real Time Clock Battery Failure (DAS)
Operator Action: Report alarm at end of day.
139
Status: Green = OK to Run
Description: Abort Evacuation Mode
Operator Action: Report alarm at end of day.
140
Description: Not currently used
141
Status: Yellow = Check as Specified
Description: Auto Switch Diesel to Electric Disabled
Operator Action: Report alarm at end of day.
142
Status: Yellow = Check as Specified
Description: Check Thermax Valve
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
143
Status: Green = OK to Run
Description: Check Remote Drain Hose Heater Output (Zone)
Operator Action: Report alarm at end of day.
144
Status: Red = Take Immediate Action
Description: Lost CAN Communications to Expansion Module
Operator Action: Unit cannot operate and is shut down. Repair immediately.
145
Status: Yellow = Check as Specified
Description: Lost Controller ON Feedback Signal
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
146
Status: Green = OK to Run
Description: Software Version Mismatch
Operator Action: Report alarm at end of day.
147
Status: Yellow = Check as Specified
Description: Check Multi-Temp Fan Speed Control Output (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
148
Status: Yellow = Check as Specified
Description: Auto Switch Electric to Diesel Disabled
Operator Action: Report alarm at end of day.
149
Status: Yellow = Check as Specified
Description: Alarm Not Identified
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
150
Status: Green = OK to Run
Description: Sensor Out of Range Low (DAS and HMI) (Zone)
Operator Action: Report alarm at end of day.
151
Status: Green = OK to Run
Description: Sensor Out of Range High (DAS and HMI) (Zone)
Operator Action: Report alarm at end of day.
152
Status: Green = OK to Run
Description: DAS Failed Sensor (DAS)
Operator Action: Report alarm at end of day.
153
Status: Green = OK to Run
Description: Expansion Module Flash Load Failure
Operator Action: Report alarm at end of day.
154
Status: Yellow = Check as Specified
Description: Low Suction Pressure Switch Failure
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
155
Status: Red = Take Immediate Action
Description: Lost CAN Communications to HMI
Operator Action: Unit cannot operate and is shut down. Repair immediately.
156
Status: Yellow = Check as Specified
Description: Check Suction/Liquid Heat Exchanger Bypass Valve
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
157
Status: Green = OK to Run
Description: OptiSet Plus Profile Mismatch
Operator Action: Report alarm at end of day.
158
Status: Green = OK to Run
Description: Primary Software Failed to Load
Operator Action: Report alarm at end of day.
159
Status: Green = OK to Run
Description: Check Battery Condition
Operator Action: Report alarm at end of day.
160
Status: Green = OK to Run
Description: Lost CAN Communications to Radio Expansion Board
Operator Action: Report alarm at end of day.
161
Status: Green = OK to Run
Description: Log DAS Real Time Clock Invalid (DAS)
Operator Action: Report alarm at end of day.
163
Status: Yellow = Check as Specified
Description: Emission Control Failure
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
175
Status: Yellow = Check as Specified
Description: Check Electronic Expansion Valve (CR)
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
176
Status: Yellow = Check as Specified
Description: Check Evaporator Pressure Sensor (CR)
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
177
Status: Yellow = Check as Specified
Description: Check CO2 Tank Pressure Sensor (CR)
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
178
Status: Yellow = Check as Specified
Description: Low CO2 Fuel Level (CR)
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
180
Status: Yellow = Check as Specified
Description: TriPac Compressor Alarm
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
188
Status: Yellow = Check as Specified
Description: Log DAS Microprocessor Fault (DAS)
Operator Action: Report alarm at end of day.
203
Status: Yellow = Check as Specified
Description: Check Display Return Air Sensor (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
204
Status: Yellow = Check as Specified
Description: Check Display Discharge Air Sensor (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
216
Status: Green = OK to Run
Description: Check DAS Digital Inputs (DAS)
Operator Action: Report alarm at end of day.
233
Status: Green = OK to Run
Description: REB Switching Off, Conservative to Full Null
Operator Action: Report alarm at end of day.
234
Status: Green = OK to Run
Description: Check Relative Humidity Sensor Circuit
Operator Action: Report alarm at end of day.
235
Status: Green = OK to Run
Description: High Engine Coolant Temperature Check
Operator Action: Report alarm at end of day.
250
Status: Green = OK to Run
Description: DAS Clock Time Reset (DAS)
Operator Action: Report alarm at end of day.
251
Status: Green = OK to Run
Description: Check Radio Expansion Board Configuration
Operator Action: Report alarm at end of day.
252
Status: Green = OK to Run
Description: Check Auto Fresh Air Exchange Circuit
Operator Action: Report alarm at end of day.
253
Status: Green = OK to Run
Description: REB On Back Up Battery, Alarms Disabled
Operator Action: Report alarm at end of day.
254
Status: Green = OK to Run
Description: Check Auxiliary Coolant Temp Sensor
Operator Action: Report alarm at end of day.
500
Status: Yellow = Check as Specified
Description: Check Host Evaporator Blower Low Speed
Operator Action: Not implemented
501
Status: Yellow = Check as Specified
Description: Check Host Evaporator Blower High Speed
Operator Action: Not implemented
505
Status: Yellow = Check as Specified
Description: Check Roadside Condenser Fan Motor Speed Circuit
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
506
Status: Yellow = Check as Specified
Description: Check Curbside Condenser Fan Motor Speed Circuit
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
507
Status: Green = OK to Run
Description: Check Digital Scroll Output Circuit (Scroll Only)
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
508
Status: Green = OK to Run
Description: Speed Request Communication Error
Operator Action: Report alarm at end of day.
509
Status: Yellow = Check as Specified
Description: ECU Failed to Enable
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
510
Status: Yellow = Check as Specified
Description: ECU Run Signal Failed
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
511
Status: Green = OK to Run
Description: Engine Wait to Start Time Delay Expired
Operator Action: Report alarm at end of day.
512
Status: Yellow = Check as Specified
Description: High Compressor Suction Pressure (Scroll Only)
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
513
Status: Yellow = Check as Specified
Description: Low Compressor Suction Ratio (Scroll Only)
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
514
Status: Yellow = Check as Specified
Description: Low Compressor Discharge Pressure (Scroll Only)
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
515
Status: Yellow = Check as Specified
Description: Minimum ETV Discharge Superheat Temp (Scroll)
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
516
Status: Red = Take Immediate Action
Description: I/O Controller to Application Controller Com Failure
Operator Action: The unit is no longer able to operate and has been shut down. Repair immediately.
518
Status: Yellow = Check as Specified
Description: Generator Ground Fault
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
519
Status: Yellow = Check as Specified
Description: Check Battery Charger Input Power
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
520
Status: Yellow = Check as Specified
Description: Check Battery Charger Output Power
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
521
Status: Yellow = Check as Specified
Description: Battery Charger External/Environmental Fault
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
522
Status: Yellow = Check as Specified
Description: Battery Temperature Sensor Alarm
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
523
Status: Yellow = Check as Specified
Description: Battery Charger Indicated Conditions
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
524
Status: Yellow = Check as Specified
Description: Generator Op Limit Vout to Frequency Ration
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
525
Status: Yellow = Check as Specified
Description: Generator Frequency Range Fault
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
526
Status: Yellow = Check as Specified
Description: Generator Operational Limit Output Current
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
528
Status: Yellow = Check as Specified
Description: Failed J1939 CAN Comm Base Controller/Charger
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
529
Status: Yellow = Check as Specified
Description: Check Fuel Pump Circuit
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
530
Status: Yellow = Check as Specified
Description: Low Pressure Differential (Scroll only)
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
531
Status: Yellow = Check as Specified
Description: Check Economizer Pressure Sensor (Scroll only)
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
538
Status: Yellow = Check as Specified
Description: Engine J1939 CAN Data Link Degraded
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
539
Status: Yellow = Check as Specified
Description: Engine J1939 CAN Data Link Failed
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
540
Status: Yellow = Check as Specified
Description: Illegal Engine Operating State
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
542
Status: Green = OK to Run
Description: Battery Charger Fault – Unit Forced to Low Speed
Operator Action: Maintenance information only. Report alarm at end of day.
543
Status: Green = OK to Run
Description: Battery Charger Internal Short
Operator Action: Maintenance information only. Report alarm at end of day.
544
Status: Green = OK to Run
Description: Battery Charger External Short
Operator Action: Maintenance information only. Report alarm at end of day.
545
Status: Green = OK to Run
Description: Battery Charger Output Voltage Exceeded Limit
Operator Action: Maintenance information only. Report alarm at end of day.
546
Status: Green = OK to Run
Description: Battery Charger Operating Bulk Voltage Out of Range
Operator Action: Maintenance information only. Report alarm at end of day.
547
Status: Yellow = Check as Specified
Description: AC Bus Phase Loss
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
548
Status: Green = OK to Run
Description: Battery Charger Temperature Below Operating Range
Operator Action: Maintenance information only. Report alarm at end of day.
549
Status: Green = OK to Run
Description: Battery Charger AC Input Overvoltage
Operator Action: Maintenance information only. Report alarm at end of day.
550
Status: Yellow = Check as Specified
Description: Battery Charger Internal Overvoltage Fault
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
551
Status: Green = OK to Run
Description: Battery Charger Internal Temp Sensor Fault
552
Status: Green = OK to Run
Description: Battery Charger Charging – Low Battery
553
Status: Green = OK to Run
Description: Battery Charger Operating Derated Due to High temp
599
Status: Green = OK to Run
Description: Engine Service Tool Connected
Operator Action: Report alarm at end of day.
600
Status: Green = OK to Run
Description: Check Crankshaft Speed Sensor
Operator Action: Report alarm at end of day.
601
Status: Green = OK to Run
Description: Check Camshaft Speed Sensor
Operator Action: Report alarm at end of day.
603
Status: Green = OK to Run
Description: Check Exhaust Pressure Sensor
Operator Action: Report alarm at end of day.
604
Status: Green = OK to Run
Description: Check Coolant Temp Sensor
Operator Action: Report alarm at end of day.
605
Status: Green = OK to Run
Description: Check Fresh Air Temp Sensor
Operator Action: Report alarm at end of day.
607
Status: Green = OK to Run
Description: Check Fuel Temperature Sensor
Operator Action: Report alarm at end of day.
608
Status: Green = OK to Run
Description: Check Rail Pressure Sensor
Operator Action: Report alarm at end of day.
609
Status: Green = OK to Run
Description: Check Intake Pressure Sensor
Operator Action: Report alarm at end of day.
610
Status: Green = OK to Run
Description: Check Atmospheric Pressure Sensor
Operator Action: Report alarm at end of day.
611
Status: Green = OK to Run
Description: Check Glow Plug Circuit
Operator Action: Report alarm at end of day.
613
Status: Green = OK to Run
Description: Check Injectors
Operator Action: Report alarm at end of day.
614
Status: Green = OK to Run
Description: Check High Pressure Fuel Pump
Operator Action: Report alarm at end of day.
615
Status: Yellow = Check as Specified
Description: Rail Pressure Fault
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
616
Status: Yellow = Check as Specified
Description: Engine Overspeed
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
617
Status: Yellow = Check as Specified
Description: Internal ECU Fault
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
618
Status: Green = OK to Run
Description: Check EGR System
Operator Action: Report alarm at end of day.
619
Status: Green = OK to Run
Description: ECU Main Relay Fault
Operator Action: Report alarm at end of day.
620
Status: Yellow = Check as Specified
Description: No RPM Detected During Start Attempt
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
623
Status: Green = OK to Run
Description: TRUCAN Message Timeout
Operator Action: Report alarm at end of day.
624
Status: Green = OK to Run
Description: Check EGR Temperature Sensor
Operator Action: Report alarm at end of day.
625
Status: Green = OK to Run
Description: Check Intake Air Temperature Sensor
Operator Action: Report alarm at end of day.
626
Status: Green = OK to Run
Description: Check Exhaust Temperature Sensor
Operator Action: Report alarm at end of day.
642
Status: Green = OK to Run
Description: ECU Forced Low Speed
Operator Action: Report alarm at end of day.
699
Status: Yellow = Check as Specified
Description: Unknown ECU Fault
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
800
Status: Green = OK to Run
Description: Crankshaft Position Sensor Error
Operator Action: Report alarm at end of day.
801
Status: Green = OK to Run
Description: Camshaft Position Sensor Error
Operator Action: Report alarm at end of day.
804
Status: Green = OK to Run
Description: Engine Coolant Temperature Sensor Error
Operator Action: Report alarm at end of day.
807
Status: Green = OK to Run
Description: Fuel Temperature Sensor Error
Operator Action: Report alarm at end of day.
808
Status: Green = OK to Run
Description: Rail Pressure Sensor Error
Operator Action: Report alarm at end of day.
809
Status: Green = OK to Run
Description: Intake Air Pressure Sensor Error
Operator Action: Report alarm at end of day.
810
Status: Green = OK to Run
Description: Atmospheric Pressure Sensor Error
Operator Action: Report alarm at end of day.
811
Status: Green = OK to Run
Description: Glow Plug Circuit Error
Operator Action: Report alarm at end of day.
813
Status: Green = OK to Run
Description: General Injector Error
Operator Action: Report alarm at end of day.
815
Status: Yellow = Check as Specified
Description: Fuel Pressure Regulator Error
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
818
Status: Green = OK to Run
Description: EGR Valve Actuator Error
Operator Action: Report alarm at end of day.
819
Status: Green = OK to Run
Description: ECU Power Relay Error
Operator Action: Report alarm at end of day.
820
Status: Green = OK to Run
Description: Main ECU Relay Error
Operator Action: Report alarm at end of day.
825
Status: Green = OK to Run
Description: T1 Air Intake Temperature Sensor Error
Operator Action: Report alarm at end of day.
826
Status: Green = OK to Run
Description: T2 Air Intake Temperature Sensor Error
Operator Action: Report alarm at end of day.
827
Status: Green = OK to Run
Description: EGR Valve Position Sensor Error
Operator Action: Report alarm at end of day.
828
Status: Green = OK to Run
Description: Lambda System Error
Operator Action: Report alarm at end of day.
829
Status: Green = OK to Run
Description: Engine Communication Error
Operator Action: Report alarm at end of day.
830
Status: Green = OK to Run
Description: Air Flow Meter Error
Operator Action: Report alarm at end of day.
832
Status: Green = OK to Run
Description: Engine Power Supply Error
Operator Action: Report alarm at end of day.
833
Status: Green = OK to Run
Description: High Pressure Pump Fuel Metering Unit Error
Operator Action: Report alarm at end of day.
834
Status: Green = OK to Run
Description: Water in Fuel Sensor Error
Operator Action: Report alarm at end of day.
836
Status: Green = OK to Run
Description: Major ECU Failures
Operator Action: Report alarm at end of day.
838
Status: Green = OK to Run
Description: Intake Air System Error
Operator Action: Report alarm at end of day.
839
Status: Green = OK to Run
Description: Engine Speed Error
Operator Action: Report alarm at end of day.
840
Status: Green = OK to Run
Description: Fuel Injection Energizing Error
Operator Action: Report alarm at end of day.
841
Status: Green = OK to Run
Description: High Pressure Pump Wear
Operator Action: Report alarm at end of day.
842
Status: Green = OK to Run
Description: Engine Running in Safe Mode – Low Speed
Operator Action: Report alarm at end of day.
843
Status: Green = OK to Run
Description: Fuel Injection System Error
Operator Action: Report alarm at end of day.
844
Status: Green = OK to Run
Description: Engine Failed to Crank
Operator Action: Report alarm at end of day.
845
Status: Green = OK to Run
Description: Starter Relay Error
Operator Action: Report alarm at end of day.
846
Status: Green = OK to Run
Description: T50 Switch Error
Operator Action: Report alarm at end of day.
847
Status: Green = OK to Run
Description: Variant Coding Error
Operator Action: Report alarm at end of day.
853
Status: Yellow = Check as Specified
Description: Engine Overspeed (No DTC)
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
854
Status: Yellow = Check as Specified
Description: Engine Protection Self Shutdown
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
899
Status: Yellow = Check as Specified
Description: Unknown ECU Fault
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
P1E
Status: Yellow = Check as Specified
Description: Return Air Temperature Sensor Fault
Operator Action: Report alarm at end of day.
P2E
Status: Yellow = Check as Specified
Description: Remote Return Air Temperature Sensor Fault
Operator Action: Report alarm at end of day.
OL
Status: Red = Take Immediate Action
Description: Electric Standby Overload
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
bAt
Status: Red = Take Immediate Action
Description: Low Battery Voltage
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
HP
Status: Red = Take Immediate Action
Description: High Discharge Pressure
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
LP
Status: Red = Take Immediate Action
Description: Low Suction Pressure
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
PSE
Status: Red = Take Immediate Action
Description: High Pressure Sensor Fault
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
tEP
Status: Red = Take Immediate Action
Description: Electric Standby Motor Thermal Protection Alarm
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
tP4
Status: Red = Take Immediate Action
Description: Power Supply Thermal Protection Alarm
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
dr1
Status: Yellow = Check as Specified
Description: Door 1 Open/Door Switch 1 Failure
Operator Action: Close door. Report alarm at end of day.
dr2
Status: Yellow = Check as Specified
Description: Door 2 Open/Door Switch 2 Failure
Operator Action: Close door. Report alarm at end of day.
tCO
Status: Red = Take Immediate Action
Description: Electronic Control Module Internal Temperature Exceeds Limit
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
SOF
Status: Red = Take Immediate Action
Description: Microprocessor Software Failure
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
- C -
Status: Red = Take Immediate Action
Description: Communications Failure, Microprocessor to In-Cab Control Box
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
From installing new trailers and truck refrigeration units to repairing current reefer units and APUs See More Services:-
- Thermo King Reefer Repair
- Carrier Reefer Repair
- Truck Repair
- Mobile Repair Service
- Pickup and Delivery Service
- Electrical Systems
- Reefer Coil Washing
- Fleet Maintenance
- Interior Truck Detailing
- Heavy Duty Truck Repair Services
- 24 Hours Towing Service
Thermo King Alarm Codes & Fault Codes
Thermo King Straight Truck Units – Most Popular
# 1 MD 200
# 2 TS 300
# 3 TS 500
# 4 RD II- SR
Thermo King Trailer Units – Most Popular
# 1 SB-III SR
# 2 SB- 210/210+
# 3 SB-310/310+
#4 SB 400
# 5 Spectrum
Thermo King Alarm Codes Defined:
- 00 NO ALARMS EXIST
- 01 MICROPROCESSOR POWER UP RESET
- 02 CHECK EVAPORATOR COIL SENSOR
- 03 CHECK RETURN AIR SENSOR
- 04 CHECK DISCHARGE AIR SENSOR
- 05 CHECK AMIBENT TEMP SENSOR
- 06 CHECK COOLANT TEMP SENSOR
- 07 CHECK ENGINE RPM SENSOR
- 08 UNIT RUNNING IN COIL SENSOR
- 09 HIGH EVAPORATOR TEMPERATURE
- 10 HIGH DISCHARGE PRESSURE (OR TEMP)
- 11 UNIT CONTROLLING ON ALTERNATE SENSOR
- 12 SENSOR OR DIGTAL INPUT SHUTDOWN
- 13 SENSOR CHECK
- 14 DEFROSAT TERMINATE BY TIME
- 15 CHECK GLOW PLUGS OR INTAKE AIR HEATER
- 16 MANUAL START NOT COMPLETED
- 17 ENGINE FAILED TO CRANK
- 18 HIGH ENGINE COOLANT TEMPERATURE
- 19 LOW ENGINE OIL PRESSURE
- 20 ENGINE ( VAPOR MOTOR CR) FAILED TO START
- 21 COOLING CYCLE CHECK
- 22 HEATING CYCLE FAULT
- 23 COOLING CYCLE FAULT
- 24 HEATING CYCLE FAULT
- 25 ALTERNATOR CHECK
- 26 CHECK REFRIGERATION CAPACITY
- 27 VAPOR MOTOR RPM HIGH (CR)
- 28 PRETIP OR SELF CHECK ABORT
- 29 DEFROST DAMPER CIRCUIT CHECK
- 31 CHECK OIL PRESSURE SWITCH
- 32 REFRIGERATION CAPACITY LOW
- 33 CHECK ENGINE RPM
- 34 CHECK MODULATION CIRCUIT
- 35 CHECK RUN RELAY CIRCUIT
- 36 ELECTRIC MOTOR FAILED TO RUN
- 37 CHECK ENGINE COOLANT LEVEL
- 38 ELECTRIC PHASE REVERSED
- 39 CHECK WATER VALVE CIRCUIT
- 40 CHECK HIGH SPEED CIRCUIT
- 41 CHECK ENGINE COOLANT TEMP
- 42 UNIT FORCED TO LOW SPEED
- 43 UNIT FORCED TO LOW SPEED MODULATION
- 44 CHECK FUEL SYATEM
- 45 CHECK HOT GAS OR HOT GAS BYPASS CIRCUIT
- 46 CHECK AIR FLOW
- 47 REMOTE SENSOR SHUTDOWN
- 48 CHECK BELTS OR CLUTCH
- 49 RESERVED FOR CR
- 50 RESET CLOCK
- 51 CHECK SHUTDOWN CIRCUIT
- 52 CHECK HEAT CIRCUIT
- 53 CHECK ECONOMIZER VALVE CIRCUIT
- 54 TEST MODE TIMEOUT
- 55 CHECK ENGINE SPEEDS
- 56 CHECK EVAPORTOR FAN LOW SPEED
- 57 CHECK EVAPORTOR FAN HIGH SPEED
- 58 CHECK CONDENSER FAN LOW SPEED
- 59 CHECK CONDENSER FAN HIGH SPEED
- 60 CHECK BOOST CIRCUIT
- 61 LOW BATTERY VOLTAGE
- 62 AMMETER OUT CALIBRATION
- 63 ENGINE OR VAPOR MOTOR STOPPED
- 64 PRETRIP REMINDER
- 65 ABNORMOL TEMPERATURE DIFFERENTIAL
- 66 LOW ENGINE OIL LEVEL
- 67 CHECK LIQUID LINE SOLENOID CIRCUIT
- 68 INTERNAL CONTROLLER FAULT CODE
- 69 CHECK REMAGNETIZATION CIRCUIT
- 70 HOURMETER FAILURE
- 71 HOURMETER 4 EXCEEDS SET TIME LIMIT
- 72 HOURMETER EXCEEEDS SET TIME LIMIT
- 73 HOURMETER 6 EXCEEDS SET TIME LIMIT
- 74 CONTROLLEER RESET TO DEFAULTS
- 75 CONTROLLER RAM FAILURE
- 76 CONTROLLER EPROM FAILURE
- 77 CONTROLLER EPROM CHECKSUM FALIURE
- 78 DATA LOG EPROM FAILURE
- 79 INTERNAL DATA LOGGER OVERFLOW
- 80 CHECK COMPRESSOR TEMP SENSOR
- 81 HIGH COMPRESSOR TEMP
- 82 HIGH COMPRESSOR TEMP SHUTDOWN
- 83 LOW ENGINE COOLANT TEMP
- 84 RESTART NULL
- 85 FORCED UNIT OPERATION
- 86 CHECK DISCHARGE PRESSURE SENSOR
- 87 CHECK SUCTION PRESSURE SENSOR
- 88 RESERVED FOR CR
- 89 CHECK ELECTRONIC THROTTLING VALVE CIRCUIT
- 90 ELECTRIC OVERLOAD
- 91 CHECK ELECTRIC READY INPUT
- 92 SENSOR GRADES NOT SET
- 93 LOW COMPRESSOR SUCTION PRESSURE
- 94 CHECK LOADER # 1 CIRCUIT
- 95 CHECK LOADER # 2 CIRCUIT
- 96 LOW FUEL LEVEL
- 97 FAILED REMOTE RETURN AIR SENSOR
- 98 CHECK FUEL LEVEL SENSOR
- 99 HIGH COMPRESSOR PRESSURE RATIO
- 100 HEATER FAN FAILURE
- 101 CONTROLLING ON EVAP COIL OUTLET TEMP
- 102 LOW EVAPORATOR COIL TEMPERATURE
- 103 LOW HEATER FUEL LEVEL
- 104 CHECK REMOTE FAN SPEED
- 105 CHECK RECEIVER TANK PRESS SOL CIRCUIT
- 106 CHECK PURGE VALVE CIRCUIT
- 107 CHECK CONDEENSOR INLET SOL CIRCUIT
- 108 DOOR OPEN TIMEOUT
- 109 CHECK HIGH DISCHARGE PRESSURE SENSOR
- 110 CHECK SUCTION LINE SOL CIRCUIT
- 111 UNIT NOT CONFIGURED CORRECTLY
- 112 CHECK REMOTE FANS
- 113 CHECK ELERCTRIC HEAT CIRCUIT
- 114 MULTIPLE ALARMS- CAN NOT RUN
- 115 CHECK HIGH PRESSURE CUT OUT SWITCH
- 116 CHECK HIGH PRESSURE CUT IN SWITCH
- 117 AUTO SWITCH FROM DIESEL TO ELECTRIC
- 118 AUTO SWITCH FROM ELECTRIC TO DIESEL
- 119 RESERVED FOR CR
- 120 CHECK ALTERNATOR EXCITE CIRCUIT
- 121 CHECK PMW LIQUID INJECTION CIRCUIT
- 122 CHECK DIESEL/ELECTRIC CIRCUIT
- 123 CHECK EVAP COIL INLET TEMP SENSOR
- 124 CHECK EVAP COIL OUTLET TEMP SENSOR
- 125 CHECK TANK LEVEL SENSOR
- 126 CHECK BACK PRESSURE REGULATOR
- 127 SETPOINT NOT ENTERED
- 128 ENGINE RUN TIME MAINT REMINDER # 1
- 129 ENGINE RUN TIME MAINT REMINDER # 2
- 130 ENGINE RUN TIME MAINT REMINDER # 1
- 131 ENGINE RUN TIME MAINT REMINDER # 2
- 132 TOTAL UNIT RUN TIME MAINT REMINDER # 1
- 133 TOTAL UNIT RUN TIME MAINT REMINDER # 2
- 134 CONTROLLER POWER ON HOURS
- 135 CHECK SPARE DIGITAL INTPUTS
- 136 CHECK SPARE DIGITAL OUTPUTS
- 137 CHECK DAMPER MOTOR HEATER OUTPUT
- 203 CHECK REDUNDANT RETURN AIR SENSOR
- 204 CHECK REDUNDANT DISCHARGE AIR SENSOR